A 3 ton heat pump equals 36,000 BTU and its amp draw varies with efficiency, compressor type, and supply voltage. This article explains typical running and startup amps, how to calculate expected current, recommended breaker and wire sizes, and practical tips for measurement and troubleshooting. Key Takeaway: Typical running amps for a 3 ton heat pump on 240V single-phase range from about 9A to 30A depending on technology; startup (inrush) can be several times higher and dictates breaker sizing and surge considerations.
Unit Type | Typical Running Amps (240V) | Typical Startup/Inrush | Recommended Breaker |
---|---|---|---|
High-Efficiency Inverter/Variable Speed | 8–15 A | 1.5–3x Running | 30 A |
Modern Single-Stage Scroll Compressor | 15–25 A | 2–4x Running | 30–40 A |
Older Standard-Stage Compressor | 20–30 A | 3–6x Running | 40–50 A |
Content Navigation
- What “3 Ton” Means And Why It Matters For Amps
- Basic Calculation: How To Estimate Amp Draw
- Why The Simple Calculation Often Underestimates Real Amps
- Typical Amp Ranges For 3 Ton Heat Pumps
- Nameplate Terms And What They Mean
- Recommended Breaker And Wire Sizes
- Startup (Inrush) Current And Its Impact
- How To Measure Actual Amp Draw
- Examples With Typical EER And SEER Values
- Auxiliary Electric Heat And Its Effect On Amp Draw
- Common Causes Of Higher-Than-Expected Amp Draw
- Troubleshooting Steps For High Amp Draw
- NEC And Safety Considerations
- When To Replace A Unit Or Upgrade Service
- Summary: Practical Guidance For Homeowners And Technicians
- Resources And Further Reading
What “3 Ton” Means And Why It Matters For Amps
“3 ton” indicates cooling capacity equivalent to melting three tons of ice in 24 hours: 36,000 BTU per hour. Electrical load depends on how much electrical power the heat pump needs to move that heat, not the tonnage alone.
A heat pump’s electrical consumption is governed by its coefficient of performance (COP) or EER/SEER ratings, compressor efficiency, and whether the unit uses variable-speed electronics. Higher efficiency reduces amp draw for the same cooling/heating capacity.
Basic Calculation: How To Estimate Amp Draw
Estimate amps by converting BTU to input kW and dividing by voltage. Use the instantaneous efficiency measure (EER) for cooling load calculations: Input kW = BTU ÷ (EER × 3412). Then Amps = kW × 1000 ÷ Voltage.
Example: 36,000 BTU with an EER of 10 on 240V: Input kW = 36,000 ÷ (10 × 3412) ≈ 1.055 kW. Amps = 1,055 W ÷ 240 V ≈ 4.4 A. This low number is theoretical because real-world EER, heat pump heat mode COP, and auxiliary heat change results; typical units show higher nameplate amps.
Why The Simple Calculation Often Underestimates Real Amps
Manufacturers list compressor and total unit nameplate amps (RLA, MCA, MOCP). RLA (Running Load Amps) and LRA (Locked Rotor Amps) differ from simple EER-based math because motors, fans, reversing valves, defrost heaters, and auxiliary electric heat draw additional current.
Electric backup heat (strip heat) in many heat pumps can add significant amps when active; a 3 ton unit might include 5 kW of strip heat drawing ~20.8 A at 240V, which must be included when sizing circuits and breakers.
Typical Amp Ranges For 3 Ton Heat Pumps
Modern inverter-driven heat pumps: 8–15 A running on 240V due to high efficiency and variable compressor speed. Startup is modest because soft-start electronics reduce inrush.
Single-stage scroll compressor units: 15–25 A running. Startup inrush can be 2–4 times running amps briefly.
Older or lower-efficiency units: 20–30 A running, with high locked-rotor currents requiring larger breakers and robust wiring.
Nameplate Terms And What They Mean
RLA (Rated Load Amps or Running Load Amps) shows typical continuous running current for the compressor only. MCA (Minimum Circuit Ampacity) is the minimum conductor size requirement. MOCP (Maximum Overcurrent Protection) indicates the maximum allowed breaker size for protection.
When evaluating expected amp draw, use MCA for conductor sizing and size breakers according to MOCP or NEC rules, considering continuous vs non-continuous loads and 125% multiplier where applicable.
Recommended Breaker And Wire Sizes
General guidelines: many 3 ton heat pumps use a 30–50 A breaker depending on model. Typical wiring choices are 10 AWG copper for up to 30 A, 8 AWG for up to 50 A. Always follow the unit’s MCA and MOCP nameplate and local code.
Typical Running Amps | Typical Breaker | Typical Wire |
---|---|---|
8–15 A | 30 A | 10 AWG Copper |
15–25 A | 30–40 A | 8–10 AWG Copper |
20–30 A | 40–50 A | 8 AWG Copper |
Startup (Inrush) Current And Its Impact
Startup current can be multiple times the running current for a short period. Inrush is highest for single-stage compressors and lower for inverter-driven units. Breakers do not trip on short inrush if within the breaker’s time-delay characteristics, but frequent large inrush may stress electrical systems.
Hard starting can also cause nuisance tripping on weak circuits or shared loads. Using a time-delay fuse or proper HVAC-rated breaker prevents nuisance trips while protecting equipment.
How To Measure Actual Amp Draw
Use a clamp-on ammeter or a true-RMS meter with current measurement. Measure at the outdoor unit’s disconnect while the unit is running in both heating and cooling modes and during compressor startup if safe to do so.
Measure with no auxiliary heat running to capture base heat pump amp draw; then measure during backup heat to capture worst-case circuit demand. Record running amps, and if possible capture peak inrush to compare with MOCP and breaker ratings.
Examples With Typical EER And SEER Values
Using EER yields better instantaneous amp estimates than SEER. Example A: 36,000 BTU at EER 11, Input kW ≈ 36,000 ÷ (11×3412) ≈ 0.96 kW → ~4 A at 240V for compressor only. Real total unit running amps rise after adding fans and controls.
Example B: 36,000 BTU at EER 8, Input kW ≈ 36,000 ÷ (8×3412) ≈ 1.32 kW → ~5.5 A. Add blower, reversing valve, and defrost elements and currents add up, bringing practical running amps into the ranges previously given.
Auxiliary Electric Heat And Its Effect On Amp Draw
Many heat pumps include auxiliary electric resistance heat for very cold weather or defrost. Auxiliary heat elements often add 2.5–10 kW, adding up to 41.7 A per 10 kW at 240V. This can more than double circuit demand and requires separate or appropriately sized circuits.
Important: When auxiliary heat runs, the total current may exceed the heat pump compressor’s MOCP, so NEC and manufacturer guidance on wire and breaker sizing must be followed.
Common Causes Of Higher-Than-Expected Amp Draw
- Dirty coils, restricted airflow, or low refrigerant charge causing compressor to work harder.
- Failing compressor motor bearings or electrical faults raising coil current draw.
- Short cycling or frequent defrost cycles increasing average amps.
- Incorrect voltage supply leading to higher current draw; low voltage increases amps for same power.
Troubleshooting Steps For High Amp Draw
Check for dirty air filters and outdoor coils and restore airflow. Verify correct refrigerant charge and inspect for leaks. Measure supply voltage under load; low voltage can raise current draw and harm compressor.
Inspect contactor, capacitor, and motor condition. Replace failing capacitors or contactors. If electrical problems persist, consult an HVAC technician or licensed electrician for diagnosis and repairs.
NEC And Safety Considerations
Follow the National Electrical Code and manufacturer nameplate when sizing conductors and overcurrent protection. NEC requires 125% of continuous load for conductor ampacity in many HVAC applications; breakers are sized per MOCP but must coordinate with wire ampacity.
Always work with or consult a licensed electrician for service, wiring changes, or breaker upgrades. Disconnect power before inspecting or working on HVAC equipment to avoid electrocution or equipment damage.
When To Replace A Unit Or Upgrade Service
Consider replacement if the unit consistently draws higher current than specified, has repeated compressor failures, or the home electrical service cannot support auxiliary heat without costly upgrades. Newer heat pumps offer significantly lower running amps due to improved inverter technology and higher efficiencies.
When upgrading to a modern inverter heat pump, evaluate service capacity, surge requirements, and whether a dedicated circuit or subpanel is needed to meet NEC and manufacturer recommendations.
Summary: Practical Guidance For Homeowners And Technicians
Estimate amps using nameplate MCA and RLA rather than raw BTU math. Typical running amps for 3 ton heat pumps on 240V usually fall in the 8–30 A range depending on technology. Startup inrush can be multiple times running current and influences breaker selection and nuisance trips.
Measure directly with a clamp meter for accurate assessment. Account for auxiliary heat when planning circuits. Always follow manufacturer nameplate values and NEC rules, and hire licensed professionals for electrical or refrigerant work.
Resources And Further Reading
Refer to manufacturer specification sheets for exact RLA, LRA, MCA, and MOCP values of specific models. Consult the National Electrical Code (NEC) and local amendments for circuit sizing and protection requirements.
For measurement and diagnostics, consider HVAC training materials and guides from industry organizations such as AHRI and NATE for correct procedures and safety practices.
Tips for Getting the Best HVAC Prices
- Prioritize Quality Over Cost
The most critical factor in any HVAC project is the quality of the installation. Don’t compromise on contractor expertise just to save money. - Check for Rebates
Always research current rebates and incentives — they can significantly reduce your overall cost. - Compare Multiple Quotes
Request at least three estimates before making your choice. You can click here to get three free quotes from local professionals. These quotes include available rebates and tax credits and automatically exclude unqualified contractors. - Negotiate Smartly
Once you've chosen a contractor, use the proven strategies from our guide — How Homeowners Can Negotiate with HVAC Dealers — to get the best possible final price.